18.16 CPU 410 cycle and reaction times
CPU 410 Process Automation/CPU 410 SMART
372 System Manual, 05/2017, A5E31622160-AC
Calculating the cycle time
The theoretical cycle time for the example is derived from the following times:
As the CPU-specific factor is 1.2, the user program execution time is:
approx. 12.0 ms
Process image transfer time (4 x double-word access and 3 x word access)
Process image: 9 µs + 7 ×25 µs = approx. 0.184 ms
Operating system runtime at scan cycle checkpoint:
approx. 0.31 ms
The total of the listed times is equivalent to the cycle time:
Cycle time
= 12.0 ms + 0.184 ms + 0.31 ms
= 12.494 ms
.
Calculation of the actual cycle time
Allowance for communication load:
12.494 ms * 100 / (10040)
= 20.823 ms
.
A time-of-day interrupt with a runtime of 0.5 ms is triggered every 100 ms.
The interrupt can be triggered a maximum of one time during a cycle:
0.5 ms + 0.490 ms (from table 16-9)
= 0.99 ms.
Allowing for communication load:
0.99 ms * 100 / (10040)
= 1.65 ms
.
20.823 ms + 1.65 ms
= 22.473 ms
.
Taking into account the time slices, the actual rounded up cycle time is
22.5 ms
.
Calculating the longest response time
Longest response time
22.5 ms * 2
= 45 ms
.
Delay of inputs and outputs
The maximum input delay of the digital input module SM 421; DI 32×DC 24 V is 4.8
ms per channel
The output delay of the digital output module SM 422; DO 16×DC 24 V/2A is
negligible.
An interference frequency suppression of 50 Hz was assigned for the analog input
module SM 431; AI 8×13Bit. The result is a conversion time of 25 ms per channel. As
8 channels are active, a cycle time of the analog input module of 200 ms results.
Analog output module SM 432; AO 8×13Bit was assigned for measuring range 0 ... 10
V. This results in a conversion time of 0.3 ms per channel. Since 8 channels are
active, the result is a cycle time of 2.4 ms. The transient time for a resistive load of 0.1
ms must be added to this. The result is an analog output response time of 2.5 ms.
All components are installed in the central controller, so DP cycle times can be ignored.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC CPU 410 and is the answer not in the manual?

Siemens SIMATIC CPU 410 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC CPU 410
CategoryControl Unit
LanguageEnglish

Related product manuals