Compatibilities between the IM 153-x
A.2 Compatibilities between the versions of IM 153-2 / -2 FO
ET 200M
244 Operating Instructions, 12/2008, EWA-4NEB780600602-08
Interface module with order number 6ES7153-…
2AA.. 2BA.. 2AB..
(FO)
2BB..
(FO)
Functions /
Properties
00 01 02 00 01/81 02/82 00 01 00
Identification and maintenance data (I&M) – – – x
(I&A)
x x – – x
(I&A)
Update via PROFIBUS DP – – – x
2
x x – – x
2
Update via SIMATIC Micro Memory Card – – – x – – – – x
RC network with 10 MΩ for unearthed
configuration
-
(1 MΩ)
as of
E03
x x x x x x x
DPV1 mode – – as of
E09
x x x – as of
E08
x
IQ-sense – – – x
(as of
FW
V3.0.1)
x x – – x
(as of
FW
V3.0.1)
E = module version
1
SYNC, FREEZE should not be used for these functions.
2
not when operating with the bus module BM IM/IM 6ES7195-7HD00-0XA0
3
supports expanded diagnostics with the 96-byte diagnostic frame in the spare part scenario
Retrofitting
You can retrofit the IM 153-2 with order number 6ES7153-2AA02-0XB0; module version 06
to the module version 07 - this is subject to a fee.
You can retrofit the IM 153-2 FO with order number 6ES7153-2AB01-0XB0, module version
05 to module version 06 - this is subject to a fee.
Contact your Siemens representative for this.
Behavior with inserting / removing interrupt
up to
153-2AA02, module version 06
153-2AB01, module version 05
as of
153-2AA02, module version 07
153-2AB01, module version 06
The ET 200M is set up on active bus modules.
The removal/insertion interrupt is disabled at
parameter assignment.
The removal or insertion of a module results in
station failure.
The ET 200M is set up on active bus modules.
The removal/insertion interrupt is disabled at
parameter assignment.
It is still, however, possible to remove and insert
modules. An interrupt is not reported, but the
events are displayed in the diagnosis.