EasyManua.ls Logo

Siemens simatic ET 200MP - Page 101

Siemens simatic ET 200MP
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
10.2 Electromagnetic compatibility
ET 200MP Distributed I/O System
System Manual, 01/2013, A5E03723484-01
101
Sinusoidal disturbances
The following table shows the electromagnetic compatibility of the ET 200MP with regard to
sinusoidal disturbances.
RF radiation
Table 10- 3 Sinusoidal disturbances with RF radiation
RF radiation in accordance with IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
Corresponds with
degree of severity
80 to 1000 MHz; 1.4 to 2 GHz 2.0 GHz to 2.7 GHz
10 V/m 1 V/m
80 % AM (1 kHz)
3
RF coupling
Table 10- 4 Sinusoidal disturbances with RF coupling
RF coupling in accordance with IEC 61000-4-6 Corresponds with
degree of severity
0.15 MHz to 80 MHz
10 V
rms
unmodulated
80 % AM (1 kHz)
150 Ω source impedance
3
Emission of radio interference
Interference emission of electromagnetic fields in accordance with EN 55016: Limit value
class A, group 1 (measured at a distance of 10 m).
Table 10- 5 Interference emission of electromagnetic fields in accordance with EN 55016
Frequency Interference emission
30 MHz to 230 MHz < 40 dB (µV/m) QP
230 MHz to 1000 MHz < 47 dB (µV/m) QP
Interference emission via the AC power supply in accordance with EN 55016: Limit value
class A, Group 1.
Table 10- 6 Interference emission via the AC power supply in accordance with EN 55016
Frequency Interference emission
0.15 MHz to 0.5 MHz < 79 dB (µV)Q
< 66 dB (µV) M
0.5 MHz to 30 MHz < 73 dB (µV)Q
< 60 dB (µV) M

Table of Contents