Technical specifications
10.3 Shipping and storage conditions
ET 200MP Distributed I/O System
102 System Manual, 01/2013, A5E03723484-01
10.3 Shipping and storage conditions
Introduction
The ET 200MP distributed I/O system exceeds requirements in terms of shipping and
storage conditions according to IEC 61131-2. The following information applies to modules
that are shipped and/or stored in their original packaging.
Shipping and storage conditions for modules
Table 10- 7 Shipping and storage conditions for modules
Type of condition Permissible range
Free fall (in shipping package) ≤ 1 m
Temperature from -40 °C to +70 °C
Barometric pressure 1080 hPa to 660 hPa
(corresponds to an altitude of -1000 m to 3500 m)
Relative humidity 5% to 95%, without condensation
Sinusoidal oscillations according to
IEC 60068-2-6
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
2
Impact according to IEC 60068-27 250 m/s
2
, 6 ms, 1000 shocks