Wiring
6.8 Front connector for the I/O modules
ET 200MP Distributed I/O System
66 System Manual, 01/2013, A5E03723484-01
Use of the potential bridges for I/O modules without shield contact element
With the delivered potential bridges, for digital modules with a maximum rated voltage of 24
V DC, you can bridge the terminals for the voltage supply and thus reduce the wiring effort.
The bridges can be inserted between the facing terminals 9 and 29, 10 and 30, 19 and 39,
and 20 and 40.
Reference
Further information on wiring the inputs and outputs can be found in the Product Manuals for
the I/O modules.
6.8.3 Wiring front connectors for I/O modules with shield contact element
Introduction
The front connector connects the I/O modules with the process signals.
Requirements
The I/O modules are installed on the mounting rail.
Wire the front connectors with the supply voltage turned off.
Follow the wiring rules (Page 57).
Prepa
re the lines, de
pending on the method of wiring.
Tools required
Stripping tool
3 to 3.5 mm screwdriver