7.2 Selection of the load power supply (PM)
ET 200MP Distributed I/O System
78 System Manual, 01/2013, A5E03723484-01
7.2 Selection of the load power supply (PM)
Introduction
The load power supply (PM) feeds the input and output circuits (load circuits) as well as the
sensors and actuators.
Properties of the load power supply
The table below shows a comparison of the various load power supply units and their
properties:
Table 7- 2 Features of load power supply units
Necessary for ... Property of the load power supplies Note
Modules that must be supplied with
voltages of ≤ 60 V DC or
≤ 250 V AC.
24 V DC load circuits
Safe electrical isolation The Siemens power supplies from the
PM 170W and SITOP series have this
feature.
24 V DC load circuits
48 V DC load circuits
60 V DC load circuits
Output voltage tolerances:
19.2 V to 28.8 V
38.4 V to 57.6 V
48 V to 72 V
-
Reference
Further information on load power supplies can be found on the Internet
(http://mall.automation.siemens.com
) in the online catalog and/or in the online ordering
system.
Short-circuit detection
Modules detect a short-circuit at the output, when the rated output current is clearly
exceeded (approx. 2x to 3x the rated output current).

Table of Contents

Other manuals for Siemens simatic ET 200MP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic ET 200MP and is the answer not in the manual?

Siemens simatic ET 200MP Specifications

General IconGeneral
BrandSiemens
Modelsimatic ET 200MP
CategoryI/O Systems
LanguageEnglish

Related product manuals