EasyManua.ls Logo

Siemens simatic ET 200MP - Wiring Front Connectors for I;O Modules Without Shield Contact Element

Siemens simatic ET 200MP
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
6.8 Front connector for the I/O modules
ET 200MP Distributed I/O System
64 System Manual, 01/2013, A5E03723484-01
The front connector is characterized by the following:
40 clamping points each
Clamping technology: Screw
If you want to supply load groups with the same potential (non-isolated), use the potential
bridges supplied for the front connector. In four locations: 9 and 29, 10 and 30, 19 and
39, 20 and 40, the terminals can be bridged by means of potential bridges. Advantage:
Reduction of the wiring effort
Note
Please note that the potential bridges may be deployed up to a maximum rated voltage of
24 V DC! The current capacity per potential bridge is 8 A maximum.
Reference
Further information on the use of the potential bridges can be found in the Product Manual
for the respective I/O module.
6.8.2 Wiring front connectors for I/O modules without shield contact element
Introduction
The front connector connects the I/O modules with the process signals.
Requirements
The I/O modules are installed on the mounting rail.
The supply voltages are turned off.
Wires are prepared according to the utilized clamping technology.
Follow the wiring rules (Page 57).
Tools required
Stripping tool