EasyManua.ls Logo

Siemens simatic ET 200MP - Page 34

Siemens simatic ET 200MP
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application planning
4.2 Power budget calculation
ET 200MP Distributed I/O System
34 System Manual, 01/2013, A5E03723484-01
Remedial measures for overload
1. Check the plant configuration, e.g.:
Is the installed power sufficient for the number and type of the I/O modules?
Is the interface module supplied on the front side with 24 V DC?
Is the interface module configured correctly (parameter "Connection to supply voltage
L+")?
Are the correct I/O modules inserted?
2. Perform corresponding changes in the configuration (e.g. insert a power supply module
before the interface module, switch on a power supply module, supply power on the front
side to the interface module, replace an I/O module).
3. The interface module periodically checks whether the connection to the backplane bus
can be recreated, and does so as soon as possible.
Exception
A power off/on of the interface module is required, for example, in the case of a voltage
drop or a hardware fault in power segment 2 or 3.
A defective power supply module must be replaced.
Proceed as follows to locate a defective I/O module in the configuration:
With the power switched off, pull the I/O modules one after the other, starting with the last
one.
After pulling each I/O module, power the interface module back on and check whether the
ET 200MP starts up without any problems.
Example of a power budget - when using the GSD
1. Find out the power provided by the interface module that is supplied with 24 V DC on the
front side (from the technical specifications of the interface module).
2. Find out the required power for the I/O modules (from the technical specifications of the
individual modules). The following example uses:
Analog output module AQ 4xU/I ST
Analog input module AI 8xU/I/RTD/TC ST
Digital output module DQ 32x24VDC/0.5A ST
Digital input module DI 32x24VDC HF
Analog output module AQ 4xU/I ST
3. Sum up the required power.
4. If the resulting value is greater than the power that is fed in by the interface module,
deploy an additional power supply (PS) module.
A power supply module before the interface module leads to a combined power
(power fed by the PS + power fed by the IM)
Each power supply module (max. 2) after the interface module spans a new power
segment (see chapter Setting up power segments (Page 36)).

Table of Contents

Other manuals for Siemens simatic ET 200MP

Related product manuals