Wiring
6.6 Connecting supply voltage to the power supply module
ET 200MP Distributed I/O System
60 System Manual, 01/2013, A5E03723484-01
Connecting supply voltage to the power supply module
Watch video sequence (http://support.automation.siemens.com/WW/view/en/67462859)
1. Swing the front cover of the power supply module up until it latches.
2. Unlock the power cable connector and remove it from the power supply module by pulling
it forward. For this purpose, press the unlocking button down (see Figure 1).
3. Loosen the screw on the front of the connector. This loosens the housing latch and the
cable relief. With a tightened screw the connector's cover can't be removed (see Figure
2).
4. Pry off the connector cover using a suitable tool (see Figure 3).
5. Strip the cable sheathing to a length of 35 mm and the conductors to a length of 7 mm,
and bring them up to the wire end ferrules.
6. Connect the wires in the connector according to the connection diagram (see Figure 4).
7. Close the cover (see Figure 5).
8. Retighten the screw (see Figure 6). This effects a strain relief on the lines.
9. Insert the power cable connector into the power supply module, until the latch engages.
Reference
Further information on making the connection can be found in the Product Manual for the
power supply module.