Parameter data records
A.4 Structure of the parameter data record 130 for user-data mapping
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
112 Manual, 12/2015, A5E36061895-AA
Error while transferring the data record
The module always checks all the values of the transferred data record. Only if all the values
were transferred without errors does the module apply the values from the data record.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for the
parameter data record 130.
Error code in STATUS parameter
(hexadecimal)
Meaning
Solution
Byte 0
Byte 1
Byte 2
Byte 3
DF 80 B0 00 Number of the data record unknown Enter a valid number for the data
record.
DF 80 B1 00 Length of the data record incorrect Enter a valid value for the data record
length.
DF 80 B2 00 Slot invalid or cannot be accessed. Check the station whether the mod-
ule is plugged or drawn.
Check the assigned values for the
parameters of the WRREC instruction
DF
80
E0
01
Incorrect version
Check Byte 0. Enter valid values.
DF 80 E0 02 Error in the header information Check Bytes 1 and 2. Correct the
length and number of the parameter
blocks.
DF 80 E1 01 Reserved bits are not 0. Check Byte 10, 11, 14, 22, 30...34,
42, 50...54, 70...74 and set the re-
served bits back to 0.
DF 80 E1 21 Parameter for user data variant not possi-
ble.
Check Byte 9. Select a different user
data variant or change the configura-
tion.
DF 80 E1 30 Invalid data record number. Check the data record number. Enter
a valid data record number.
DF 80 E1 31 Parameter for length of the parameter
block invalid.
Check Byte 1. Length = 10 bytes
DF 80 E1 32 Parameters for number of parameter
blocks invalid.
Check Byte 2. Enter valid values.
DF 80 E1 33 Parameter for measured value ID invalid. Check Bytes 4 and 5. Enter valid
values.
DF 80 E1 3B Parameter for user data variant impermis-
sible.
Check Byte 1. Number for user-
specific user data variant has to be
01
H
.

Table of Contents

Other manuals for Siemens simatic et200sp

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens simatic et200sp and is the answer not in the manual?

Siemens simatic et200sp Specifications

General IconGeneral
CategoryI/O Systems
Power Supply24 V DC
Protection RatingIP20
Number of ModulesUp to 64 modules
MountingDIN Rail
Communication ProtocolsPROFINET, PROFIBUS
Storage Temperature-40 °C to +70 °C
Digital InputsYes (depending on module)
Digital OutputsYes (depending on module)
Analog InputsYes (depending on module)
Analog OutputsYes (depending on module)
ModularityModular
Relative Humidity5 to 95% (non-condensing)
WeightVaries by configuration
System TypeDistributed I/O