User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
141
Total energy L1L2L3 (ID 249 or F9
H
)
Table D- 7 Total energy L1L2L3
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
249 (F9
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2
Reserved
BYTE
-
-
-
3
Reserved
BYTE
-
-
-
4 ... 7
Total active energy inflow L1L2L3
UDINT
1 Wh
0 … 4294967295
220
8 ... 11
Total active energy outflow L1L2L3
UDINT
1 Wh
0 … 4294967295
221
11 ... 15
Total reactive energy inflow L1L2L3
UDINT
1 varh
0 … 4294967295
222
16 ... 19
Total reactive energy outflow L1L2L3
UDINT
1 varh
0 … 4294967295
223
20 ... 23
Total apparent energy L1L2L3
UDINT
1 VAh
0 … 4294967295
224
24
Reserved
BYTE
-
-
-
25
Scaling active energy, inflow
USINT
-
0 ... 255
-
26
Scaling active energy, outflow
USINT
-
0 ... 255
-
27
Scaling reactive energy, inflow
USINT
-
0 ... 255
-
28
Scaling reactive energy, outflow
USINT
-
0 ... 255
-
29
Scaling apparent energy
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Total power factor L1L2L3
USINT
0.01
0 … 100
66037