User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
142 Manual, 12/2015, A5E36061895-AA
Energy L1 (ID 248 or F8
H
)
Table D- 8 Energy L1
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
248 (F8
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L1
UINT
1 mA
0 … 65535
66007
4 ... 7
Active energy inflow L1
UDINT
1 Wh
0 … 4294967295
62110
8 ... 11
Active energy outflow L1
UDINT
1 Wh
0 … 4294967295
62111
11 ... 15
Reactive energy inflow L1
UDINT
1 varh
0 … 4294967295
62112
16 ... 19
Reactive energy outflow L1
UDINT
1 varh
0 … 4294967295
62113
20 ... 23
Apparent energy L1
UDINT
1 VAh
0 … 4294967295
62114
24
Scaling current L1
USINT
-
0 ... 255
-
25
Scaling active energy inflow L1
USINT
-
0 ... 255
-
26
Scaling active energy outflow L1
USINT
-
0 ... 255
-
27
Scaling reactive energy inflow L1
USINT
-
0 ... 255
-
28
Scaling reactive energy outflow L1
USINT
-
0 ... 255
-
29
Scaling apparent energy L1
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Power factor L1
USINT
0.01
0 … 100
66019