User data variants
D.1 User data variants with 32 bytes input data / 12 bytes output data
Analog input module AI Energy Meter 480VAC ST (6ES7134-6PA20-0BD0)
Manual, 12/2015, A5E36061895-AA
143
Energy L2 (ID 247 or F7
H
)
Table D- 9 Energy L2
Byte
Allocation
Data type
Unit
Value range
Measured
value ID
0
User data variant
BYTE
-
247 (F7
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L2
UINT
1 mA
0 … 65535
66008
4 ... 7
Active energy inflow L2
UDINT
1 Wh
0 … 4294967295
62210
8 ... 11
Active energy outflow L2
UDINT
1 Wh
0 … 4294967295
62211
11 ... 15
Reactive energy inflow L2
UDINT
1 varh
0 … 4294967295
62212
16 ... 19
Reactive energy outflow L2
UDINT
1 varh
0 … 4294967295
62213
20 ... 23
Apparent energy L2
UDINT
1 VAh
0 … 4294967295
62214
24
Scaling current L2
USINT
-
0 ... 255
-
25
Scaling active energy inflow L2
USINT
-
0 ... 255
-
26
Scaling active energy outflow L2
USINT
-
0 ... 255
-
27
Scaling reactive energy inflow L2
USINT
-
0 ... 255
-
28
Scaling reactive energy outflow L2
USINT
-
0 ... 255
-
29
Scaling apparent energy L2
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Power factor L2
USINT
0.01
0 … 100
66020