Commissioning the device
4.3 Parameterizing the Comfort Panel
Comfort Panels
144 Operating Instructions, 08/2018, A5E36770603-AC
Alarms of type "Warning" with options:
Icon
Status
Alarm
Meaning
Overwrite Select project data
The following lines contain options for overwriting
data on the HMI device.
Recipes
Overwrite recipes of the HMI device with the
recipes of the project (optional).
User administration
data
Overwrite the user administration on the HMI
device with the user administration of the project
(optional).
Upgrade Runtime upgrade
Runtime version on the HMI device is older than
the Runtime version of the project, versions are
compatible, upgrade of Runtime version on the
HMI device is optional.
Upgrade Firmware upgrade
Firmware version on the HMI device is older than
the firmware version of the project, versions are
compatible, upgrade of firmware on the HMI
device is optional.
Downgrade Runtime downgrade
Runtime version on the HMI device is newer than
the Runtime version of the project, versions are
compatible, downgrade of Runtime version on the
HMI device is optional.
Downgrade Firmware downgrade
Firmware version on the HMI device is newer
than the firmware version of the project, versions
are compatible, downgrade of firmware on the
HMI device is optional.
Alarms of type "Error" with option:
Icon
Status
Alarm
Meaning
Upgrade Runtime upgrade
Runtime version on the HMI device is older than
the Runtime version of the project, versions are
incompatible, upgrade of Runtime version on the
HMI device is required.
Upgrade Firmware upgrade
Firmware version on the HMI device is older than
the firmware version of the project, versions are
incompatible, upgrade of firmware on the HMI
device is required.
Downgrade Runtime downgrade
Runtime version on the HMI device is newer than
the Runtime version of the project, versions are
incompatible, downgrade of Runtime version on
the HMI device is required.
Downgrade Firmware downgrade
Firmware version on the HMI device is newer
than the firmware version of the project, versions
are incompatible, downgrade of firmware on the
HMI device is optional.
Download Runtime download There is no Runtime software on the HMI device,
e.g. after update of the operating system.
Runtime software must be downloaded.