Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
90 Function Manual, 10/2018, C79000-G8976-C387-04
Structure of the configuration data attachment of "WRITE-CONFIG"
For RF61xR/RF68xR and RF18xC:
When CONFIG = 0x01:
Reset_Reader; LEN_DATA = 0x00
When CONFIG = 0x03:
When replacing a module, it is possible to read all the configuration data from the
CM/reader and to store it on the controller. When the module is replaced, this data can
then be loaded on the reader from the controller. The command "WRITE-CONFIG" (0x03)
is used for the download to the CM/reader and "READ-CONFIG" for the upload from the
reader.
Byte
Name
0
Structure identifier (2 bytes)
2 Length information (4 bytes)
Length of the version identifier and parameter block
6 Version identifier (4 bytes)
Based on the identifier, you can uniquely identify the configuration.
This is a time stamp in Linux format.
The time stamp indicates how many seconds have passed since
January 1, 1979, 00:00 (midnight). The identifier is assigned when a
configuration is generated.
10 ... end "DATA"
Parameter block
LEN_DATA = Size of the configuration data + 6 bytes
When CONFIG = 0x80:
The structure of the send buffer corresponds to that of the block "Set_Param (Page 45)".
LEN_DATA = 0x08
For RF200, RF300, RF620R, RF630R, MOBY D/U
Table 3- 74 For RF200, RF300, RF620R, RF630R, MOBY D/U when "CONFIG = 0x03"
Byte
1
2...5
1)
6
2)
7...8
9
10
11
12
13...14
15
16
Value
0x04 0x00 0x0A
0x05
0x00 scanning_
time
param op-
tion_1
distance_
limiting
No. of
tran-
sponders
field_on_
control
field_on_
time
1)
In the communications module RF180C as of V2.2 in conjunction with MOBY U byte 4 is preset with the calendar week
and 5 with the year.
2)
With the readers named in the title of the table the value "0x0A" (LEN_DATA = 0x10) is used in byte 6. In the MOBY I
migration in RF300 readers of the second generation the value "0x05" (LEN_DATA = 0x0B) is used.