Setting parameters for blocks
3.5 Programming the Ident profile
Ident profile and Ident blocks, standard function for Ident systems
Function Manual, 10/2018, C79000-G8976-C387-04
91
Table 3- 75 Bytes of the "PARAM" parameter
Byte
Value
RFID system
Meaning
Byte 9
scanning_
time
RF200,
RF300,
MOBY D
0x00 (reserved)
RF600 "scanning_time" describes the radio profile according to EPC Global. Set the cor-
rect standard according to the country in which you want to operate the reader.
Please check which standard and which reader variant is applicable to your coun-
try before you select a wireless profile.
Value
Description
ETSI
FCC
CMIIT
0x00 No standard selected; the
error "0x15" is output
-- -- --
0x01 Reader works with the de-
fault wireless profile. Value
of the default wireless profile:
ETSI new FCC China
0x02 ETSI new: EU, EFTA, Tur-
key;
4-channel plan
X -- --
0x03 ETSI old: EU, EFTA, Turkey;
readers commissioned after
December 31, 2009, must
not be operated with this
setting.
X -- --
0x04 FCC: e.g. USA, Canada,
Mexico
-- X --
0x05
Reserved
--
--
--
0x06
China
--
--
0x07 Thailand -- X --
0x08
Brazil
--
X
--
0x09
South Korea
--
X
--
0xC0
India
X
--
--
Note: If you select country profiles other than those defined for the particular read-
er variant, the error message "09" is acknowledged.
MOBY U "scanning_time" describes the standby time for the transponder. If the transponder
receives a further command before "scanning_time" has expired, this command
can be executed immediately. If the transponder receives a command after "scan-
ning_time" has expired, command execution is delayed by the "sleep_time" of the
transponder.
"scanning_time" should only be set when
the transponder is processed with several commands and
the execution must be completed within a minimum time.
Note that the "scanning_time" affects the working life of the battery. The longer
"scanning_time" is, the shorter the life of the battery. For precise calculations, see
the MOBY U manual for configuration, mounting and service.
Value
Description
0x00
No standby time (default)
0x01
7 ms standby time
0x02 14 ms standby time