Service and maintenance
12.2 Error messages
SIMATIC RF650R/RF680R/RF685R
294 Configuration Manual, 03/2018, C79000-G8976-C386-06
"ER"
LED
XML/
LED
(hex)
PLC block
(hex)
Error description
2 Hz 0x63 0xE6FE03
• A parameter of an XML command has an invalid value or the parameter assignment of
the communications module or the reader was incorrect.
Possible causes / action to be taken:
– Check the parameters in the Ident profile.
– Check the relevant XML command.
– Check the parameter assignment in HW Config / STEP 7 (TIA Portal).
– The "WRITE-CONFIG" command has incorrect parameter settings.
– After a startup, the reader or communications module has still not received an
"INIT".
• The parameter assignment of the reader or communications module on
PROFIBUS/PROFINET was incorrect and the command cannot be executed.
Possible causes / action to be taken:
– Length of the input/output areas is too small for the cyclic I/O word.
– Check whether you have used the correct GSD file.
– User data length set with the command (e.g. "READ") is too high.
• Error when processing the command.
Possible causes / action to be taken:
– The data in "AdvancedCmd" or "IID_CMD_STRUCT" is incorrect (e.g. "WRITE"
command with length = 0).
Check "AdvancedCmd" or "IID_CMD_STRUCT" and execute an "INIT".
– The hardware of the reader/communications module is defective. The reader or
communications module receives bad data with an "INIT".
– The AB byte does not match the user data length.
• The wrong reset block was selected.
Possible causes / action to be taken:
– Regardless of the selected reader system, use the "Reset_Reader" function block.
-- 0x64 0xE6FE04 Presence error
A transponder has passed through the transmission window of a reader without being pro-
cessed.
• This error message is not reported immediately. Instead, the reader or communications
module waits for the next write / read command. This command is replied to immediate-
ly with this error and the write/read command is not executed. The next command is ex-
ecuted normally again by the reader/communications module.
• You can reset this error status using an "INIT".
• Bit 2 is set in the "OPT1" parameter and there is no transponder in the transmission
window.

Table of Contents

Other manuals for Siemens SIMATIC RF650R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC RF650R and is the answer not in the manual?

Siemens SIMATIC RF650R Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC RF650R
CategoryOther
LanguageEnglish

Related product manuals