STEP 5 Operations S5-115F Manual
3.1.3 Load and Transfer Operations
Use load and transfer operations to do the following:
Exchange information between various operand areas
Prepare times and counts for further processing
Load constants for program processing
Information flows indirectly via accumulators (ACCUM 1 and ACCUM 2). The accumulators are
special registers in the CPU for temporary storage. In the S5-115F they are each 16 bits long. The
accumulators are structured as shown in Figure 3-1.
ACCUM 2 ACCUM 1
Low byteHigh byte Low byteHigh byte
15 8 7 0
15
8 7
0
Figure 3-1. Accumulator Structure
You can load and transfer permissible operands in bytes or words.
For exchange in bytes, information is stored right-justified, i.e., in the low byte.
The remaining bits are set to zero.
You can process the information in the two accumulators using various operations.
Load and transfer operations are executed independently of condition codes. Execution of these
operations does not affect the condition codes.
You can program load and transfer operations graphically only in combination with timer or
counter operations; otherwise you can represent them only in STL form.
Table 3-3 provides an overview of the load and transfer operations.
3-10
EWA 4NEB 811 6149-02

Table of Contents

Other manuals for Siemens SIMATIC S5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S5 and is the answer not in the manual?

Siemens SIMATIC S5 Specifications

General IconGeneral
Product type designationSIMATIC S5
Programming languageSTEP 5
Digital inputsVaries by model
Digital outputsVaries by model
Analog inputsVaries by model
Analog outputsVaries by model
Supply voltage24V DC
CPU TypeVaries by model
MemoryVaries by model
Digital I/OVaries by model
Analog I/OVaries by model
CommunicationPROFIBUS
Operating Temperature0°C to 60°C
Relative Humidity5% to 95% (non-condensing)

Related product manuals