Configuring with COM 115F S5-115F Manual
The following prompt appears in the case of digital modules when you select a byte with 'B':
”DELETE BYTE(S)”.
The rules for word numbers also apply to the input of byte numbers but for the fact that all
integers between 0 and 127 can be used here. When you delete, you remove all bits in the
byte from 0 to 7. In order to delete a single bit, you need only press the space bar when the
cursor is on the type number.
After the parameters have been entered, the ”DELETE?” message appears. You can initiate
execution of the function by pressing the <Exec> key, and you can abort the function by
pressing the <Break> key, and returning to the initial state for type entry. If you press only
<CR> in reply, the routine will be aborted and you will be returned to the initial state for
type entry. This completes parameter setting in the analog area.
F5 Types
This softkey routine gives you an overview of the available type selection ( 1.2.1).
Starting from the initial state for type entry, the cursor is located in an element of the type
configuration field. The system expects you to enter a valid type number at this position. At
this point in the program, it is possible to transfer the types offered for selection together
with their individual characteristics into the second window of the configuration form using
the F5 softkey.
To do so, start with the lowest valid type number and fade in each subsequent type by
pressing the <Types> function key.
When the last valid type has been reached, the first is displayed again.
You can enter further type numbers after each change in the type display.
A typical type and characteristics field is shown in Figure 1-22.
Type number : 3
Num. of I/O channels : 2
Safety-related : Yes
Intermittent : No
Feedback module required :
Check DQ 1/2 chann.
DB number (4 to 255): 13
Signal group (0 to 28): 2
Interrupt generating (Y/N): N
Inp. volt. (24/220): 24 V
Discrepancy time (S/L): S 30 msec.
CH DQ Channel No. (1/2): 2
CH DQ Byte addr. (0 to 125): 120
Figure 1-22. Characteristics Field of I/O Type 3
F6 Save
This function is used to save data from the configuration level on diskette or hard disk. If no
program file has been defined in the System Handling menu or in the Defaults menu, the
B:@@@@@FST.S5D program file is used. If this is the case, select the Handling menu with
the <RETURN> key and enter the file name there. Finally, store the data.
1-36
EWA 4NEB 811 6149-02

Table of Contents

Other manuals for Siemens SIMATIC S5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S5 and is the answer not in the manual?

Siemens SIMATIC S5 Specifications

General IconGeneral
Product type designationSIMATIC S5
Programming languageSTEP 5
Digital inputsVaries by model
Digital outputsVaries by model
Analog inputsVaries by model
Analog outputsVaries by model
Supply voltage24V DC
CPU TypeVaries by model
MemoryVaries by model
Digital I/OVaries by model
Analog I/OVaries by model
CommunicationPROFIBUS
Operating Temperature0°C to 60°C
Relative Humidity5% to 95% (non-condensing)