STEP 5 Operations S5-115F Manual
3.7 Programming Notes
In order to guarantee the safety of systems requiring official authorization, the possibility of
systematic errors by the user must be precluded. Systematic errors have the same effect on both
subunits.
Note
Organize your programs as clearly as possible!
The following are not permitted
Trick programming
Linking of Boolean logic operations to actions on different parentheses levels
The hardware does not monitor the parenthesis stack for overflow.
The use of the operations DI, and JUR in safety-oriented programs.
3.8 LPLZ Incrementing Sequence
Operating system
Monitoring measures are integrated.
User program
An operation sequence for incrementing the logical program counter must be inserted at the
latest every 128 statements/operations in order to guarantee proper program execution in both
subunits.
The program is monitored by the logical program counter (LPLZ). It is located in FW 0 and must be
incremented by the user program at the latest after 127 codewords.
The following rule applies for structured programming with blocks:
The sequence for incrementing the LPLZ is located at the beginning of each block
Blocks longer than 127 words are segmented with ”BLD 255”
The BLD 255 operation before the 127 word boundary is followed by the LPLZ sequence
(10 bytes)
- LFW0
- LKF+1
-+F
- TFW0
Flag word 0 must not be used by the user in any other way.
3-76
EWA 4NEB 811 6149-02

Table of Contents

Other manuals for Siemens SIMATIC S5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S5 and is the answer not in the manual?

Siemens SIMATIC S5 Specifications

General IconGeneral
Product type designationSIMATIC S5
Programming languageSTEP 5
Digital inputsVaries by model
Digital outputsVaries by model
Analog inputsVaries by model
Analog outputsVaries by model
Supply voltage24V DC
CPU TypeVaries by model
MemoryVaries by model
Digital I/OVaries by model
Analog I/OVaries by model
CommunicationPROFIBUS
Operating Temperature0°C to 60°C
Relative Humidity5% to 95% (non-condensing)

Related product manuals