S5-115F Manual Application
7.5 Transferring the Configuration Data to the PLC
In test mode, you can transfer the configuration data from the hard disk or the diskette to the PLC.
Proceed as follows:
Connect the programmer to subunit A
Call the ”Defaults” screen form and enter the following:
Name of the program file
Operating mode ”ON”
Call the ”System handling” screen form and press F3 ”TRAN/LOAD”.
You are now in the ”Transfer/Load I/O” menu.
Press F3 ”LOAD FD”
The configuration is now loaded into the programmer memory from the hard disk or diskette.
Press F2 ”Tran PLC”
Press F1 ”Config. DB”
The configuration is now loaded into the PLC memory from the programmer memory.
You are now in the ”Transfer” menu
Press F8 ”Return” and
terminate the input.
The complete configuration is now in the PLC.
You can now load your control program into the PLC memory and try out the program in test
mode.
EWA 4NEB 811 6149-02
7-11

Table of Contents

Other manuals for Siemens SIMATIC S5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S5 and is the answer not in the manual?

Siemens SIMATIC S5 Specifications

General IconGeneral
Product type designationSIMATIC S5
Programming languageSTEP 5
Digital inputsVaries by model
Digital outputsVaries by model
Analog inputsVaries by model
Analog outputsVaries by model
Supply voltage24V DC
CPU TypeVaries by model
MemoryVaries by model
Digital I/OVaries by model
Analog I/OVaries by model
CommunicationPROFIBUS
Operating Temperature0°C to 60°C
Relative Humidity5% to 95% (non-condensing)

Related product manuals