Application S5-115F Manual
Change the following standard values:
Second error occurrence time : 1 * 10 min
Update user time: Max. interval : 16383 * 10 min (no monitoring)
Interrupt proc.: Max. interval : 255 * 10 msec (no monitoring)
Short discr. time interr. DI : 0 msec (not required)
Short discr. time analog input : 0 * 10 msec (not required)
DB No. for long discr. times : 0 (no long discrepancy times)
Min. absolute AI deviation : 0 (not required)
Press F6 ”SAVE”. The parameters just set are then stored in the program file.
Terminate initialization of the operating system.