EasyManua.ls Logo

Siemens SIMATIC TI555 - Resistance below Minimum; Resistance above Maximum

Siemens SIMATIC TI555
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
7-15
TI545/TI555 System Manual
Checking RS-485 (Twisted Pair) Cable Installation (continued)
Line-to-line
resistance that is below the minimum specified in T
able 7-3
may be caused by the following:
Incorrect termination resistors are installed.
More than two termination resistors are installed.
There is a short in the cable.
Line-to-shield resistance that is below the minimum specified in T
able 7-3
may be caused by the following:
One of the 9-pin connectors is connected to an RBC or CPU.
Cable line wires are shorted to the shield.
Line-to-line resistance that is above the maximum specified in T
able 7-3
may be caused by the following:
Incorrect termination resistors are installed.
Fewer than two termination resistors are installed.
The cable is open between the point of measurement and one or both of
the termination resistors.