EasyManua.ls Logo

Siemens SIMATIC TI555 - Connecting a CPU Drop Line; Figure 4-4 Connecting to Terminal Block

Siemens SIMATIC TI555
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-9
Cabling and Wiring the System
TI545/TI555 System Manual
4. Strip
back 1.50 in. (3.8 cm) of the sleeving on the other end of the cable.
5.
Remove 0.13 in. (0.33 cm) of each color
-coded insulation to expose the
bare wires.
6.
Install each wire end onto a terminal lug according to directions
provided by the vendor
.
NOTE:
The size of the terminal lug depends on the type of terminal block
used. Consult your vendor for the appropriate terminal lug size.
Use the following procedure to connect a drop line cable between the
programmable controller and terminal block.
1.
Ensure that the cable has been prepared as described on page 4-8.
2.
Plug the cable D-connector onto the CPU I/O connector
.
3. T
ighten two cable connector screws to secure the cable D-connector to
the CPU I/O connector
.
4.
Loosen three terminal screws on the terminal block and install the
cable lug terminals onto the terminal block. See Figure 4-4.
From
TI545/TI555
Figure 4-4 Connecting
to T
er
minal Block
5. T
ighten terminal block screws.
Connecting a CPU
Dr
op Line

Table of Contents

Related product manuals