Control functions
7.8 Communicating with the PLC
SINAMICS V90, SIMOTICS S-1FL6
Operating Instructions, 04/2019, A5E36037884-007
279
8 Reserved - Reserved -
Enable master control from the PLC
Enable master control from the PLC
Direction of rotation reversal
Note
The following signals are occupied by Modbus control word when you use the setpoint and
control word from Modbus as the Modbus control source (p29008 = 1). They can only be
enabled by Modbus co
ntrol word while cannot be enabled by external DI terminals.
PTI/Fast PTI control mode: SON
IPos control mode: SON, SREF (REF for reference mode 0)
S control mode: SON, CWE/CCWE
T control mode: SON
Note
In IPos control mode, when the relative positioni
ng mode is selected, the method for
accepting MDI setpoint must be a rising edge (bit 5 = 0); otherwise, fault F7488 occurs.
Note
In IPos control mode, when you implement the absolute positioning for the modular axis with
Modbus, you can select the MDI
direction with parameter p29230.
Note
In T control mode, the motor cannot be stopped with OFF1 via Modbus.
Note
All the reserved bits in register 40100 must be set to 0.