If you cannot determine the cause, contact the Hotline and provide this code and the
diagnostics data.
RESET state (permanent RESET)
In the RESET state, the CPU of the D4x5-2 is in a permanent RESET, i.e.
No software is running (D4x5-2 operating system is stopped) and
The hardware is in a state that produces less power loss
This state occurs, for example, if the max. module temperature has been greatly
exceeded.
The state is displayed as follows:
The RDY LED flashes red/yellow at 2 Hz
The 7-segment display shows "8"
Possible measures:
Correct the causes of any overtemperature.
Ensure that the 24 V supply is stable without any power dips.
Insert the fan/battery module.
The state can only be exited by switching the D4x5-2 off and on.
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
388 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B