EasyManuals Logo

Siemens SIMOTION CX32-2 Commissioning And Hardware Installation Manual

Siemens SIMOTION CX32-2
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #388 background imageLoading...
Page #388 background image
If you cannot determine the cause, contact the Hotline and provide this code and the
diagnostics data.
RESET state (permanent RESET)
In the RESET state, the CPU of the D4x5-2 is in a permanent RESET, i.e.
No software is running (D4x5-2 operating system is stopped) and
The hardware is in a state that produces less power loss
This state occurs, for example, if the max. module temperature has been greatly
exceeded.
The state is displayed as follows:
The RDY LED flashes red/yellow at 2 Hz
The 7-segment display shows "8"
Possible measures:
Correct the causes of any overtemperature.
Ensure that the 24 V supply is stable without any power dips.
Insert the fan/battery module.
The state can only be exited by switching the D4x5-2 off and on.
Diagnostics
9.1 Diagnostics via LED displays
SIMOTION D4x5-2
388 Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B

Table of Contents

Other manuals for Siemens SIMOTION CX32-2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOTION CX32-2 and is the answer not in the manual?

Siemens SIMOTION CX32-2 Specifications

General IconGeneral
BrandSiemens
ModelSIMOTION CX32-2
CategoryControl Unit
LanguageEnglish

Related product manuals