Table 6- 40 Control logic parameters of the motor holding brake
Enables extended parameter access
P1215 = …
Enable motor holding brake
0 Motor holding brake locked (factory setting)
1 Motor holding brake enabled
2 Motor holding brake with voltage boost enabled
P0346 = …
0 ... 20 s, factory setting 1 s
P1080 = …
0 … 650 Hz, (0 Hz factory setting): minimum motor frequency, regardless of frequen-
P1216 = …
Delay time for opening the brake
0 ... 20 s, factory setting 0.1 s
Note: P1216> brake release time + relay opening time
P1217 = …
Holding time after runout
0 ... 20 s, factory setting 0.1 s
Note: P1217> brake closing time + relay closing time
P1227 = …
Zero value detection monitoring time
0 ... 300 s, factory setting 4 s
Opening the motor holding brake via P1218
Using parameter P1218, you can force the brake to open, e.g. in order to be able to
manually move a conveyor drive.
Secure loads held by the brake!
Since this procedure cancels the "Brake active" signal which, in turn, causes the brake to
be forced open, the user must ensure that, even when the motor has been powered-down,
all loads held by the brake are secured before the signal is canceled.
Table 6- 41 Parameter to force open a motor holding brake
Enable expert access to parameters
Forcibly open the motor holding brake