EasyManua.ls Logo

Siemens SINAMICS G110D - Restoring the factory settings

Siemens SINAMICS G110D
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5.2 Restoring the factory settings
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
63
5.2
Restoring the factory settings
If nothing else works, restore the factory settings!
You can restore the factory settings using parameter P0970.
Parameter or proce-
dure
Description
P0003 = 1
User access level
1: Standard level
P0010 = 30
Commissioning parameter
30: Factory setting, parameter transfer
P0970 = 1
Restore factory settings
1: Restore the factory parameter settings
IOP - select factory
restart from the extras
menu.
The IOP will display a message stating that a factory reset is taking place
and display a progress bar. When completed the display will display a mes-
sage that the factory reset has been successfully completed.
STARTER
Displays a progress bar.
Note
Data tra
nsfer is interrupted while the factory parameter settings are being restored.
The following parameters remain unchanged even after the factory settings have been
restored:
P0014 Storage mode
P0100 Europe / North America
P0201 Power stack code number
Communication parameters
Power-Module-specific data