Commissioning
5.2 Restoring the factory settings
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
63
Restoring the factory settings
If nothing else works, restore the factory settings!
You can restore the factory settings using parameter P0970.
P0003 = 1
P0010 = 30
30: Factory setting, parameter transfer
P0970 = 1
1: Restore the factory parameter settings
IOP - select factory
restart from the extras
The IOP will display a message stating that a factory reset is taking place
and display a progress bar. When completed the display will display a mes-
sage that the factory reset has been successfully completed.
nsfer is interrupted while the factory parameter settings are being restored.
The following parameters remain unchanged even after the factory settings have been
restored:
P0014 Storage mode
P0100 Europe / North America
P0201 Power stack code number
Communication parameters
Power-Module-specific data