SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
205
The inverter has the capability to identify internal and external fault conditions, the most
common faults are shown in the following tables. More detailed information on faults can be
found in the Parameter List.
Table 8- 1 Fault codes description
F00001
Overcurrent - Motor power does not correspond to the inverter power
Check that the motor and inverter power ratings are the same.
F00002 Cause Overvoltage - mains supply voltage too high or motor is in regenerative
mode.
Check the mains supply voltage
F00003
Undervoltage - mains / 24 V supply has failed
Check mains supply / 24 V supply
F00004 Cause Inverter over temperature - the inverter has exceeded the temperature
Remedy Check motor loading, pulse frequency setting, ambient temperature or if
fitted the fan is working correctly.
F00030
Fain no longer working - replace fan.
F00041
Motor data identification failure
Remedy check that the motor is connected to the inverter correctly and that the
motor data entered is correct.
F00062
Recopy data to SD card and ensure that the process is completed.
F00070 Cause PLC setpoint fault - the communications failure monitoring times, set by
Remedy Check:
• If the AS-interface master has stopped or is in 'program' mode.
• The cable connection between the bus nodes.
• check if the communication monitoring time has been set too short in
P2040.
F00071
USS setpoint fault - no setpoint values from USS during telegram off time.
Remedy Check and improve monitoring timing using STARTER
F00073 Cause Control Panel setpont fault - no setpoint values from Control Panel during
Remedy
• Check and improve - if necessary - the value in P3984
• Acknowledge fault
• If fault persists, contact Service Department or change Inverter.