Appendix A
A.1 Electromagnetic compatibility
SINAMICS G110D
216 Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
EMC performance
EMC Emissions
The SINAMICS G110D inverters have been tested in accordance with the emission
requirements of the category C2 (domestic) environment.
Table A- 2 Conducted & Radiated Emissions
Radiated Emissions EN 55011 Class A
Note
To achieve this performance the default switching frequency should not be exceeded and
the recommended cables and connectors should be fitted correctly.
Achieving radiated emissions to EN 55011 Class B is largely dependent on the inverter
being correctly installed inside a metallic enclosure. The limits will not be met if the inverter is
not enclosed or installed in accordance with good EMC practices.
The harmonic current emissions from the SINAMICS G110 D inverters is as follows:
Table A- 3 Harmonic Currents
Typical Harmonic Current (% of rated input current)
FSA … FSC
(400 V, 0.75 kW … 7.5 kW)
73 52 25 23 22 15 12 10
Note
Units installed within the category C2 (domestic) environment require supply authority
acceptance before connection to the public low
-voltage power supply network. Please
contact your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.