Commissioning
5.5 Factory settings for the Inverter
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
67
Factory settings for the Inverter
Default command and setpoint sources
Inverters used in automation solutions have the appropriate fieldbus interfaces. These
Inverters are preset in the factory so that the appropriate control and status signals can be
exchanged using the fieldbus interface.
Table 5- 1
Command and setpoint sources
P0700 = 6
Select the command source
P1000 = 3
Select the setpoint source
Fixed frequencies
Table 5- 2
Factory setting of additional important parameters
Meaning of the factory setting
P0003 1
Access to the most frequently used
parameters
Selecting the user access level 1
P0004 0 All parameters are displayed Parameter filter: filters parameters in ac-
cordance with the functionality
1
P0100 0 Europe [50 Hz] Frequency of the regional supply network
• IEC, Europe
• NEMA, North America
1
P0300 1 Induction motor Select the motor type (induction motors /
2
P0304 400 [V] Rated motor voltage
(in accordance with rating plate in V)
1
P0305 depends on
the
[A] Rated motor current
(in accordance with rating plate in A)
1
P0307 depends on
the
[kW/hp] Rated motor output
(in accordance with the rating plate in
1
P0308 0 [cos phi] Rated motor power factor (in accordance
with rating plate in cos 'phi') when P0100 =
1.2, then P0308 is irrelevant
1
P0309 0 [%] Rated motor efficiency (in accordance with
rating plate in %) when P0100 = 0, then
1
P0310 50 [Hz] Rated motor frequency
(in accordance with rating plate in Hz)
1
P0311 1395 [rpm] Rated motor speed
(in accordance with rating plate in rpm)
1