Introduction
2.2 Adapting the Inverter to the application
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
21
2.2.3
Parameters with follow-on parameterization
When you change certain parameters, the system may automatically change other
parameters accordingly. This makes it much easier to parameterize complex functions.
Example: Parameter P0700 (command source)
Parameter P0700 can be used to switch the command source from the fieldbus to digital
inputs. When the value of P0700 is changed from 6 (command source "fieldbus") to 2
(command source "digital inputs"), other parameter values are changed automatically:
New functions are assigned to the digital inputs (P0701 ... P0704)
Inverter control is interconnected with the signals from the digital inputs (P0800, P0801,
P0840, etc.)
For more information about follow-on parameterization for P0700, see the List Manual.
2.2.4
Frequently required parameters
Parameters that in many cases help
Table 2- 1
This is how you filter the parameter list to keep the number of displayed parameters to a minimum
Parameter
Description
P0003 =
User access level
1: Standard: Allows access to the most frequently used parameters (factory setting)
2: Extended: Extended access, e.g. to inverter I/O functions
3: Expert: To be used by experts
P0004 =
Parameter filter
0: All the parameters are displayed (factory setting).
2: Inverter
3: Motor - data of the motor and output filter are displayed
Table 2- 2
How to switch to commissioning mode or restore the factory setting
Parameter
Description
P0010 =
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
30: Factory setting - initiate restore factory settings
Table 2- 3
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:

Table of Contents

Related product manuals