Functions
6.9 Technological functions
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
145
Automatic restart characteristics
Table 6- 44 Overview of the automatic restart characteristics
P1210
ON command always active (continuously)
ON command in the de-energized
state
Fault F0003 due to
All other faults
Inverter
signals a fault
Before power fail-
ure
Inverter ready
Before power
failure
Power
failure
Line supply
undervoltage
Before
power failure
in
operation
0
--*
--*
--*
--*
--*
--*
1 Fault acknowl-
edgement
--*
Fault acknowl-
edgement
--*
Fault acknowl-
edgement
--*
2 Fault acknowl-
edgement +
restart
--*
--*
--*
--*
Restart
3 Fault acknowl-
edgement +
restart
Fault acknowl-
edgement
+ restart
Fault acknowl-
edgement +
restart
Fault acknowl-
edgement +
restart
Fault acknowl-
edgement
+ restart
--*
4 Fault acknowl-
edgement +
restart
Fault acknowl-
edgement
+ restart
--*
--*
--*
--*
5 Fault acknowl-
edgement +
restart
--*
Fault acknowl-
edgement +
restart
--*
Fault acknowl-
edgement + restart
Restart
6 Fault acknowl-
edgement +
restart
Fault acknowl-
edgement + restart
Fault acknowl-
edgement +
restart
Fault acknowl-
edgement +
restart
Fault acknowl-
edgement + restart
Restart
*) -- = no action