Functions
6.9 Technological functions
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
147
Input values
Table 6- 45 Main function parameters
Parameter
Description
P1200 =
Flying restart
0: locked (factory setting),
1 - 6 Active
Table 6- 46 Overview: the "flying restart" function
P1200
Flying restart active
Search direction
0 Flying restart locked (factory setting) -
1 Flying restart always active Search performed in both directions, startup in
direction of setpoint
2 Flying restart active after:
Power ON
Faults
OFF2
Search performed in both directions, startup in
direction of setpoint
3 Flying restart active after
Faults
OFF2
Search performed in both directions, startup in
direction of setpoint
4
Flying restart always active
Search performed in direction of setpoint only
5 Flying restart is active after
Power ON
Faults
OFF2
Search performed in direction of setpoint only
6 Flying restart is active after
Faults
OFF2
Search performed in direction of setpoint only
Table 6- 47 Additional commissioning parameters
Parameter
Description
P1202 =
Motor current: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Defines the search current with respect to the rated motor current (P0305) that is pre-
sent when the "flying restart" function is used.
P1203 =
Search rate/speed: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Sets the factor by which the output frequency changes during the flying restart to syn-
chronize itself with the running motor.