Connection
4.7 SINAMICS G110D Specifications
SINAMICS G110D
46 Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Max current rating of circuit
breaker (A)
SINAMICS G110D SCCR for
group installation using cir-
cuit breakers
6SL3511-.PE24-0AM. 30
3RV2721 50 kA, 480 Y / 277 V AC
6SL3511-.PE25-5AM. 30
6SL3511-.PE27-5AM. 30
Table 4- 10 Type E combination motor controllers (NKJH) for group installation
SINAMICS G110D SCCR for group instal-
lation using CMC
6SL3511-.PE17-5AM.
6SL3511-.PE21-5AM.
6SL3511-.PE23-0AM.
6SL3511-.PE24-0AM.
6SL3511-.PE25-5AM.
6SL3511-.PE27-5AM. 3RV2021-4DA.. 25 15 65 kA, 480 V AC
*Where “_” in the CMC model no. can be replaced by “1” or “2”.
Listed (NKJH) Siemens CMCs of the same type with a current rating lower than that
specified in the table, corresponding to SINAMICS G110D drive model number and with a
voltage rating of at least 480 V AC may also be used.