Connection
4.8 Cables and connections
SINAMICS G110D
50 Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Table 4- 14 Motor connector
Belcom
"DESINA"
Cable No.
All connector parts are Harting Q8/0
1 mm
2
18 AWG
13EBN17Z08P Harting Q8/0
0912 008
3001
1 mm
2
18 AWG
0933 000 6105 1912 008 0502 1912 000 5057
3.00 kW 2.5 mm
2
14 AWG
13EBN13Z08P 2.5 mm
2
14 AWG
0933 000 6102 1912 008 0528 Lapp
MS-SC-
M25x1.5
53112640
4 mm
2
12 or 10
13EBN11Z08P 4 mm
2
12 or 10
0933 000 6107
7.50 kW
4 x crimps are required for each inverter for the motor connections; use 75°C copper wire only
Table 4- 15 Temperature sensor and EM brake
Belcom
"DESINA"
Cable No.
1 mm
2
18 AWG
13EBN17Z08P 0.75 mm
2
20 AWG
0933 000 6114 0.75 mm
2
20 AWG
0933 000 6114
2.5 mm
2
14 AWG
13EBN13Z08P 1 mm
2
18 AWG
0933 000 6105 1 mm
2
18 AWG
0933 000 6105
4 mm
2
12 or 10
13EBN11Z08P 1 mm
2
18 AWG
0933 000 6105 1.5 mm
2
18 AWG
0933 000 6104
7.50 kW
2 x crimps are required for each auxiliary signal pair; use 75°C copper wire only
Connection specifications
Danger to life when live parts are touched in the motor terminal box
Hazardous voltage can be present on the pins for temperature sensor and motor holding
brake. Touching live parts on the motor cable and in the motor terminal box can lead to
death due electrical shock.
• Keep the motor terminal box closed whenever the mains is applied to the converter.
• Insulate the cables that are not used.
• Use appropriate insulation on the cables.