Advanced commissioning
7.2 Inverter control
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
125
In the above example, use digital input 3 to switch from one control system of the converter
via digital inputs to a control system via the fieldbus.
An overview of all the parameters that belong to the command data sets is provided in the
List Manual.
Note
The converter requires
approx. 4 ms to switch over the command data set.
To change the number of command data sets in STARTER, you must open your STARTER
project offline.
You can edit command data sets if, in the STARTER project tree, you select "Configuration".
If you require more than two command data sets, then add command data sets using this
,
To simplify commissioning several command data sets, under the "Command data sets" tab
there is a copy function.
Figure 7-6 Editing command data sets in STARTER
Drive commissioning: Data sets
p0170
Number of command data sets
(factory setting: 2)
Drive commissioning: Ready
Displaying the number of the CDS that is currently active
Number of the command data set to be copied (source)
Number of the command data set to which the data is to be copied (target)
p0809[2] = 1
Copying is started
Once copying has been completed, the inverter sets p0809[2] to 0.
Command data set selection CDS bit 0
Command data set selection CDS bit 1
Displaying the number of the CDS that is currently active