Advanced commissioning
7.7 Protection functions
Converter with control units CU250D-2
232 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
7.7.3
Protecting the motor by calculating the motor temperature
The converter calculates the motor temperature based on a thermal motor model.
Requirements
The inverter can only calculate a realistic motor temperature if the following requirements are
met:
Perform basic commissioning
In the basic commissioning, set the motor data via the motor code, the motor Article No.,
or according to the motor nameplate.
Check the value of the motor mass (P0344). The inverter calculates the p0344 based on
the basic commissioning.
Settings
Table 7- 24 Parameters for temperature acquisition without using a temperature sensor
Parameter
Description
p0601
Motor temperature sensor type
(factory setting: 0)
0: No sensor
p0604
Mot_temp_mod 2/KTY Warning threshold
(factory setting: 130 °C)
Threshold for monitoring the motor temperature
.
.
After exceeding the threshold, the converter reports fault F07011.
p0605
Mot_temp_mod 1/2 threshold
(factory setting: 145 °C)
Threshold for monitoring the motor temperature with motor temperature model 1, 2, or
KTY
.
Motor temperature model 1 (p0612.0 = 1): Alarm threshold - If the alarm threshold is
exceeded, the inverter reports alarm A07012.
Motor temperature model 2 (p0612.1 = 1) or KTY: Fault threshold - If the fault thresh-
old is exceeded, the inverter reports fault F07011.
p0610
Motor overtemperature response
(factory setting: 12)
Determines the behavior as soon as the motor temperature reaches the warning
threshold p0604.
0:
Warning (A07910), no fault.
1: Warning (A07910); current limit will be reduced and timer started. Shutdown
with fault (F07011).
2:
Warning (A07910); timer is started. Shutdown with fault (F07011).
12: As for 2 but the last shutdown temperature is used to calculate the motor
temperature (factory setting).
p0611
I2t motor model thermal time constant
(factory setting: 0 s)
The parameter is only effective for synchronous motors.
On selecting a motor from the motor list (p0301), the converter sets up the parameter
value automatically.