Installation
4.2 Electrical Installation
Converter with control units CU250D-2
54 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
4.2.14
Grounding converter and motor
Grounding the converter
Ground the converter via the PE connection in the mains supply connector.
Ground the connectors as shown in the diagram below.
Figure 4-16 Grounding the line supply and motor connectors
Connect the PE terminal on the left-hand
side of the converter to the metal frame it is
mounted on.
Recommended cable cross section: 10 mm²
Use a short wire connection preferably.
Clean the connection to the steel
construction from paint or dirt.
Use a ring clamp to ensure a good physical
connection which is resistant to accidental
disconnection.
Grounding the motor
Ground the motor via the PE connection in the motor connector.
Ground the connector as shown in the diagram above (grounding the converter).
Although the line and motor connectors are of a different type, the principle of grounding
them is the same.
If possible, ground the motor housing.