EasyManua.ls Logo

Siemens SINAMICS G120D - Identification & Maintenance Data (I&M)

Siemens SINAMICS G120D
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarms, faults and system messages
10.4 Identification & maintenance data (I&M)
Converter with control units CU250D-2
330 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
10.4
Identification & maintenance data (I&M)
I&M data
The inverter supports the following identification and maintenance (I&M) data.
I&M
data
Format
Explanation
Associated
parameters
Example for the
content
I&M0 u8[64] PROFIBUS
u8[54] PROFINET
Inverter-specific data, read only - See below
I&M1 Visible String [32] Plant/system identifier p8806[031] "ak12-
ne.bo2=fu1"
Visible String [22]
Location code
p8806[3253]
"sc2+or45"
I&M2 Visible String [16] Date p8807[015] "2013-01-21
16:15"
I&M3
Visible String [54]
Any comment
p8808[053]
-
I&M4 Octet String[54] Check signature to track chang-
es for Safety Integrated.
This value can be changed by
the user.
The test signature is reset to the
value generated by the machine
is p8805 = 0 is used.
p8809[053] Values of
r9781[0] and
r9782[0]
When requested, the inverted transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP 7, STARTER or TIA-Portal.
I&M0
Designation
Format
Example for the
content
Valid for
PROFINET
Valid for
PROFIBUS
Manufacturer-specific
u8[10]
0000 hex
---
MANUFACTURER_ID u16 42d hex
(=Siemens)
ORDER_ID Visible String
[20]
„6SL3246-0BA22-
1FA0“
SERIAL_NUMBER Visible String
[16]
„T-R32015957“
HARDWARE_REVISION
u16
0001 hex
SOFTWARE_REVISION
char, u8[3]
„V“ 04.70.19
REVISION_COUNTER
u16
0000 hex
PROFILE_ID
u16
3A00 hex
PROFILE_SPECIFIC_TYPE
u16
0000 hex
IM_VERSION
u8[2]
01.02
IM_SUPPORTED
bit[16]
001E hex

Table of Contents

Other manuals for Siemens SINAMICS G120D

Related product manuals