Advanced commissioning
7.6 Basic positioner and position control
Converter with control units CU250D-2
198 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
7.6.7.4
Set reference point
Description
Position the load, e.g. using the "jog" function, at the reference position in the machine.
Figure 7-40 Set reference point
Activate 'set home position'
Precondition
You have selected the "Homing" screen.
Procedure
To activate 'set home position', proceed as follows:
1. Interconnect this bit with the corresponding signal of your machine.
If the axis is stationary, with the signal change 0 1, the inverter sets its actual position
value to the reference point coordinate.
For this function, all of the other signals are of no significance.