EasyManua.ls Logo

Siemens SINAMICS G120D - Advanced Settings

Siemens SINAMICS G120D
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advanced commissioning
7.5 Motor control
Converter with control units CU250D-2
160 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Advanced settings
Parameter
Explanation
p1226
Standstill detection, speed threshold
(Factory setting: 20 rpm)
The moment of inertia estimator only measures the load torque for speeds ≥ p1226.
p1226 also defines from which speed the inverter switches-off the motor for OFF1
and OFF3.
p1560
Moment of inertia estimator accelerating torque threshold value
(factory setting:
10 %)
p1561
Moment of inertia estimator change time inertia
(factory setting: 500 ms)
The lower that p1561 or p1562
is, the shorter the moment of
inertia estimator measure-
ments.
The larger p1561 or p1562 is,
the more accurate the results
provided by the moment of
inertia estimator.
p1562
Moment of inertia estimator change time load
(facto-
ry setting: 10 ms)
p1563
Moment of inertia estimator load torque positive direction of rotation
(factory setting:
0 Nm)
p1564
Moment of inertia estimator load torque negative direction of rotation
(factory setting:
0 Nm)
p5310
Moment of inertia precontrol configuration (factory setting: 0000 bin)
.00
1 signal: activates calculation of the characteristic (p5312p5315)
.01
1 signal: activates moment of inertia precontrol
p5310.00 = 0, p5310.01 = 0
Deactivating moment of inertia precontrol
p5310.00 = 1, p5310.01 = 0
Adapting the moment of inertia precontrol
p5310.00 = 0, p5310.01 = 1 Activating the moment of inertia precontrol.
The characteristic of the moment of inertia
precontrol remains unchanged.
p5310.00 = 1, p5310.01 = 1
Activating the moment of inertia precontrol. The
inverter adapts the characteristic in parallel.
r5311
Moment of inertia precontrol status word
.00 1 signal: New measuring points for the characteristic of the moment of inertia
precontrol are available
.01
1 signal: new parameters are been calculated
.02
1 signal: moment of inertia precontrol active
.03 1 signal: the characteristic in the positive direction of rotation has been calcu-
lated and is ready
.04 1 signal: the characteristic in the negative direction of rotation has been calcu-
lated and is ready
.05
1 signal: The inverter writes actual results to the parameter
p5312
Moment of inertia precontrol linear positive
(factory
setting: 0 1/s
2
)
In a positive direction of rota-
tion:
Moment of inertia = p5312 ×
load torque + p5313
p5313
Moment of inertia precontrol constant positive
(fac-
tory setting: 0 kgm
2
)
p5314
Moment of inertia precontrol linear negative
(factory
setting: 0 1/s
2
)
In a negative direction of rota-
tion:
Moment of inertia = p5314 ×
load torque + p5315
p5315
Moment of inertia precontrol constant negative
(factory setting: 0 kgm
2
)

Table of Contents

Other manuals for Siemens SINAMICS G120D

Related product manuals