EasyManua.ls Logo

Siemens SINAMICS G120D - Introduction, V;F Control, Vector Control

Siemens SINAMICS G120D
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
5.2 Preparing for commissioning
Converter with control units CU250D-2
62 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
5.2.2
Introduction, V/f control, vector control
Specifying the control mode
The converter has three open-loop control and closed-loop control modes for induction
motors:
Open-loop control with U/f-characteristic (U/f control)
Field-oriented control (sensorless vector control)
Speed control (vector control with encoder)
The control modes have different degrees of suitability when it comes to controlling a
position-controlled axis:
Vector control with encoder
Sensorless vector control
U/f control
With the position control, provides the best
results
Limited functionality of the position
control.
Low accuracy
Travel to fixed stop is not possi-
ble
Not recommended in conjunction
with position control.
Low accuracy
Low dynamic response
Travel to fixed stop is not possi-
ble
It is not permissible to use vector control in the following cases:
If the motor is too small in comparison to the inverter (the rated motor power may not be
less than one quarter of the rated inverter power)
If several motors are connected to one inverter
If a power contactor is used between the inverter and motor and is opened while the
motor is powered up
If the maximum motor speed exceeds the following values:
Inverter pulse frequency
2 kHz
4 kHz and higher
Pole number of the motor
2-pole
4-pole
6-pole
2-pole
4-pole
6-pole
Maximum motor speed [rpm]
9960
4980
3320
14400
7200
4800

Table of Contents

Other manuals for Siemens SINAMICS G120D

Related product manuals