Technical data
11.6 Current derating - depending on the installation altitude
Converter with control units CU250D-2
350 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
11.6
Current derating - depending on the installation altitude
Current derating depending on the installation altitude
Above 1000 m above sea level you must reduce the inverter output current as a result of the
lower cooling capability of the air.
Permissible line supplies depending on the installation altitude
Installation altitude up to 2000 m above sea level
Connection to every supply system permitted for the inverter.
Installation altitudes between 2000 m and 4000 m above sea level
Connection to a TN system with grounded neutral point.
TN systems with grounded line conductor are not permitted.
The TN line system with grounded neutral point can also be supplied using an
isolation transformer.
The phase-to-phase voltage does not have to be reduced.
Note
690 V Power Modules
For 690 V Power Modules, the TN line system must be established with grounded neutral
point through an isolating transformer.