Advanced commissioning
7.6 Basic positioner and position control
Converter with control units CU250D-2
168 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Setting the modulo range
Preconditions
● You are online with the STARTER .
● You have selected the "Mechanical system" screen.
To set the modulo range, proceed as follows:
1. Enable the modulo correction.
2. Define the modulo range.
Example 1: In the case of a rotary table, one load revolution corresponds to 3600 LU. In
this case, the modulo correction is also 3600.
Example 2: For a roller conveyor, 100 motor revolutions corresponds to one production
cycle. For a resolution of 3600 LU per motor revolution, the modulo range is 360000 LU.
You have now set the modulo range.
Modulo offset, modulo range
Modulo correction activation (signal = 1)