Technical data
11.9 Electromagnetic Compatibility
Converter with control units CU250D-2
354 Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
Note
Install all drives in accordance with the manufacturer’s guidelines and in accordance with
good EMC practices.
le type CY. The maximal cable length is 15 m.
Do not exceed the default switching frequency 4
kHz.
Table 11- 7 Conducted disturbance voltage and radiated emissions
Level acc. to
IEC 61800-3
Conducted emissions
(disturbance voltage)
All converters with integrated class A filters.
Order number:
First Environment -
Professional Use
Radiated emissions Converter frame sizes A, B and C with integrated
class A filter.
Order number:
6SL3525-0PE17-*
**
6SL3525-0PE21-*
**
6SL3525-0PE23-*
**
6SL3525-0PE24-*
**
6SL3525-0PE25-*
**
6SL3525-0PE27-*
**
In a domestic environment this product may cause
radio interference in which case supplementary miti-
gation measures may be required.
First Environment -
Professional Use
Table 11- 8 Harmonic Currents
Typical Harmonic Current (% of rated input current) at U
K
1 %
Note
Units installed within the category
C2 (domestic) environment require supply authority
acceptance for connection to the public low
-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.