A.8 Acceptance tests for the safety functions
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
383
3.
3.1. Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
When controlled via
PROFIsafe
When controlled via fail-
safe digital inputs (F-DI)
When controlled via
terminals STO_A and
STO_B on Power Mod-
• The inverter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
• The inverter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
• The inverter signals
the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)
• If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
• The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
• The inverter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
4.
4.2.
• STO is not active (r9773.1 = 0).
• The inverter signals neither faults nor alarms of the safety functions
(r0945[0…7], r2122[0…7]).
You have performed the acceptance test of the STO function.