Commissioning
5.5 Restoring the factory setting
Converter with control units CU250D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
85
Procedure with Startdrive
Proceed as follows to reset the inverter to factory settings:
1. Go online.
2. Select "Commissioning".
3. Select "Backing up/reset".
4. Select "All parameters are reset".
5. Press the "Start" button.
You have reset the inverter to factory settings.
Procedure with operator panel
Proceed as follows to reset the inverter to factory settings:
1. Select the "Extras" menu
2. Select the "Parameter settings" menu
3. Select the entry "Restore drive to factory settings"
You have reset the inverter to factory settings.