Diagnosis
Diagnostics using LEDs
6-196
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
6.1.4 Smart Line Module 5 kW and 10 kW
Table 6-5 Smart Line Module 5 kW and 10 kW – description of LEDs
LED
Color Status Description, cause Remedy
OFF
Electronics power supply is missing or outside
permissible tolerance range.
Green Continuous Module is ready.
READY
Red Continuous
Overtemperature.
Overcurrent switch off.
Diagnose fault
(via output
terminals) and
acknowledge
(via input
terminal)
OFF
Electronics power supply is missing or outside
permissible tolerance range.
DC LINK
Yellow Continuous
DC link voltage within permissible tolerance
range.
DC
LINK
Red Continuous
DC link voltage outside permissible tolerance
range.
Supply failure.
Check supply
voltage