Communication via PROFIBUS
Cyclic communication
4-93
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
4.3.2 Description of control words and setpoints
Note
This chapter describes the assignment and meaning of the process data in
SINAMICS interface mode (p2038 = 0).
The reference parameter is also specified for the relevant process data. The
process data is generally normalized in accordance with parameters p2000 to
r2004. A temperature of 100 °C = 100% and an electrical angle of 90° also =
100%. For more information, see Section 7.4.
Overview of control words and setpoints
Table 4-2 Overview of control words and setpoints
Abbre-
viation
Name Signal no. Data type
1)
Interconnection
parameters
CTW1 Control word 1 1 U16 (bit serial)
2)
CTW2 Control word 2 3 U16 (bit serial)
2)
NSETP_A Speed setpoint A (16-bit) 5 I16 p1070
NSETP_B Speed setpoint B (32-bit) 7 I32 p1155
p1430(DSC)
G1_CTW Encoder 1 control word 9 U16 p0480[0]
G2_CTW Encoder 2 control word 13 U16 p0480[1]
G3_CTW Encoder 3 control word 17 U16 p0480[2]
XERR Position deviation 25 I32 p1190
KPC Position controller gain factor 26 I32 p1191
TRQRED Torque reduction 101 I16 p1542
A_CTW1 Control word for A_INF/B_INF (infeed) 320 U16 (bit serial)
2)
1) Data type to PROFIdrive Profile V3.1:
I16 = Integer16, I32 = Integer32, U16 = Unsigned16, U32 = Unsigned32
2) Bit-serial interconnection: see the following pages